beautypg.com

NORD Drivesystems BU0700 User Manual

Page 90

background image

NORDAC SK 700E Operating Manual

90

Subject to technical alterations

BU 0700 GB-1411

Parameter

Setting value / Description / Note

Available with option

P509

Interface

always visible

0 ... 21

[ 0 ]

Selection of the interface via which the FI is controlled. (P503: Note Master function output!)

0 = Control terminals or keyboard control **/*** with the Control Box (Option), the Parameter Box

(Option, not ext. p-box), the Potentiometer Box (Option) or via Bus I/O Bits (Option)

1 = Control terminals only */***, the FI can only be controlled via the digital and analog inputs ( a

customer unit is necessary!) or via the BUS I/O Bits (Option).

2 = USS setpoint */***, the frequency setpoint is transferred via the RS485 interface. Control via the

digital I/Os is still active.

3 = USS control word *, the control signals (enable, rotation direction, etc.) are transferred via the

RS485 interface, the setpoint via the analog input or the fixed frequencies.

4 = USS *, all control data is transferred via the RS485 interface. The analog and digital inputs have

no function. The setting is required for the external p-box!

5 = CAN setpoint */*** (Option)

6 = CAN control word * (Option)

7 = CAN * (Option)

8 = Profibus setpoint */*** (Option)

9 = Profibus control word * (Option)

10 = Profibus * (Option)

11 = CAN Broadcast * (Option)

12 = InterBus setpoint */*** (Option)

13 = InterBus control word * (Option)

14 = InterBus * (Option)

15 = CANopen setpoint */*** (Option)

16 = CANopen Control word * (Option)

17 = CANopen * (Option)

18 = DeviceNet setpoint */*** (Option)

19 = DeviceNet Control word * (Option)

20 = DeviceNet * (Option)

21 = in preparation

*) Keyboard control (ControlBox, ParameterBox, PotentiometerBox) is blocked, parameterisation is still
possible.

**) If the communication during keyboard control is interrupted (time out 0.5 sec), the FI will block
without error message.

***) Permissible settings for using the AS interface.

P510

Interface bus setpoints

always visible

0 ... 8

[ 0 ]

Selection of the interface via which the FI is controlled.

0 = Auto (=P509): The source of the auxiliary setpoint is

automatically derived from the setting in the parameter
P509 >Interface<

1 = USS

2 = CANbus

3 = Profibus

4 = InterBus

5 = CANopen

6 = DeviceNet

7 = Reserved

8 = CAN Broadcast

P511

USS baud rate

always visible

0 ... 3

[ 3 ]

Setting of the transfer rate (transfer speed) via the RS485 interface. All bus subscribers must have the
same baud rate setting.

0 = 4800 baud

1 = 9600 baud

2 = 19200 baud

3 = 38400 baud

P512

USS address

always visible

0 ... 30

[ 0 ]

Setting for the inverter address.

Note:

For details about the respective Bus
systems: please refer to the respective
Options descriptions.

BU 0020 = Profibus

BU 0050 = USS

BU 0060 = CAN/CANopen

BU 0070 = InterBus

BU 0080 = DeviceNet

BU 0090 = AS-Interface