3.1 Technology unit
BU 0700 GB-1411
Subject to technical alterations
27
Controlling the frequency inverter with the ParameterBox
The frequency inverter can only be completely controlled via the ParameterBox if the parameter >Interface< (P509) is set to the
>Keyboard< function (0 or 1) (the factory setting of the NORDAC SK 700E) and the inverter is not enabled via the control
terminal.
vector
R
No inverter
control function
Increase frequency
Store actual frequency
Decrease frequency
STOP (Enable)
Change rotation direction
START (Enable)
Note:
If the inverter is enabled in this mode, then the parameter set to be used can be selected for this inverter in the
menu: >Parameterisation< ...>Basic Parameter< in the parameter >Parameter Set<.
If the parameter set has to be changed during operation, then the new parameter set must be selected in this
parameter and activated using the
keys.
Attention:
After the START command, the inverter can start immediately or with a pre-programmed frequency (minimum
frequency P104 or jog frequency P113).
Parameterising with the ParameterBox
The parameter mode accessed is the one selected at menu item >Parameterisation< at Level 1 of the Parameter Box. The
parameter level of the connected inverter is accessed using the ENTER key.
The diagram below shows how the ParameterBox control elements are used for parameterisation.
vector
R
Increase value
Simultaneous activation:
load default parameters
One menu level forward
or
accept parameter value
Reduce value
Selection back
Simultaneous operation
one menu level back
Selection forward
SELECTION keys
VALUE keys