NORD Drivesystems BU0700 User Manual
Page 112
NORDAC SK 700E Operating Manual
112
Subject to technical alterations
BU 0700 GB-1411
Display
Error
Cause
Remedy
Group
Detail in
P700 / P701
13.2
Slip error switch-off monitoring
"Safe stop" was carried out
Torque limit (P112) was reached, switch-off or increase as
necessary.
Current limit (P536) was reached, switch-off or increase as
necessary.
Check motor data (motor circuit, stator resistance)
If necessary, check incremental encoder data (P3xx)
E014
14.0
Slave check
PosiCon - Error 1
Further details can be found in the description BU 0710
14.1
Host check
14.2
Reference point travel error
14.3
Absolute encoder voltage
monitoring bit
14.4
Absolute encoder error
14.5
Position change and speed do
not match
14.6
Slip error between absolute and
incremental encoders
14.7
Maximum position exceeded
14.8
Minimum position undershot
E015
15.0
Incorrect software version
PosiCon - Error 2
Further details can be found in the description BU 0710
15.1
Watchdog PosiCon
15.2
Stack overflow PosiCon
15.3
Stack underflow PosiCon
15.4
Undefined opcode PosiCon
15.5
Protected instruction PosiCon
15.6
Illegal word access PosiCon
15.7
Illegal instruction access PosiCon
15.8
EPROM error PosiCon
E016
16.0
Motor phase error
A motor phase is not connected.
Check P539
16.1
Motor current monitoring for
braking mode
Required exciting current not achieved at moment of switch-on.
Check P539
Check motor connection
E017
17.0
Customer unit change
New or missing customer unit
Switch mains voltage off and then on again