5 line choke (accessories), Tb2 b1 l1 l2 – NORD Drivesystems BU0700 User Manual
Page 12
NORDAC SK 700E Operating Manual
12
Subject to technical alterations
BU 0700 GB-1411
2.5 Line choke (accessories)
To reduce input side current harmonics, additional inductivity
can be installed into the line supply to the inverter.
These chokes are specified for a maximum supply voltage of
480V at 50/60 Hz.
The protection class of the chokes is IP00 and they must
therefore be installed in a control cabinet.
For frequency inverters with an output of 45 kW or more, a
line choke is recommended where several devices are being
used, in order to avoid possible adverse effects of one device
on another. In addition, the charging currents (mains voltage
fluctuations) are significantly reduced.
Inverter type
NORDAC
SK 700E
Input choke 3 x 380 - 480 V
Length
L1
Width
B1
Depth
T
Detail: mounting
Conn
e
c
tio
n
Type
Permanent
current
Inductance
Length
L2
Width
B2
M
ou
nti
n
g
1.5 ... 2.2 kW
SK CI1-460/6-C
6 A
3 x 4.88 mH
71
125
140
55
100
M4
4
3.0 ... 4.0 kW
SK CI1-460/11-C
11 A
3 x 2.93 mH
84
155
160
56.5
130
M6
4
5.5 ... 7.5 kW
SK CI1-460/20-C
20 A
3 x 1.47 mH
98
190
201
57.5
170
M6
10
11 ... 18.5 kW
SK CI1-460/40-C
40 A
3 x 0.73 mH
118
190
201
77.5
170
M6
10
22 ... 30 kW
SK CI1-460/70-C
70 A
3 x 0.47 mH
124
230
220
98
180
M6
35
37 ... 45 kW SK CI1-460/100-C
100 A
3 x 0.29 mH
148
230
290
122
180
M6
50
55 ... 75 kW SK CI1-460/160-C
160 A
3 x 0.18 mH
170
299
360
105
237
M8
95
90 ... 132 kW SK CI1-460/280-C
280 A
3 x 0.10 mH
190
290
270
133
240
M10
150
160 kW SK CI1-460/350-C
350 A
3 x 0.084 mH
190
300
270
107
224
M8
CU Bar
All dimensions in [mm]
[mm
2
]
T
B2
B1
L1
L2
1
3
4
2
5
6