7 technical data, 1 general data – NORD Drivesystems BU0700 User Manual

Page 114

background image

NORDAC SK 700E Operating Manual

114

Subject to technical alterations

BU 0700 GB-1411

7 Technical data

7.1 General Data

Function

Specification

Output frequency

0.0 ... 400.0 Hz

Pulse frequency

1.5 to 7.5kW: 3.0 ... 20.0kHz (Standard = 6kHz = Nominal power 100% ED)

11 - 37kW: 3.0 ... 16.0kHz (Standard = 6kHz = Nominal power 100% ED)

45 to 110kW: 3.0 ... 8.0kHz (Standard = 4.0kHz = Nominal power 100% ED)

132kW/160kW: 4.0kHz

Typical overload capacity

1.5...22kW:
150% for 60s, 200% for 3.5s

30...132kW:
150% for 60s

(Pulse switch-off P537)

SK 700E-163-340-O-VT:

Max. 125% for 60s (> 5Hz)

Max. 80...125% for 60s

(0...5Hz)

Protective measures against

Overtemperature of the frequency inverter

Over and under-voltage

Short-circuit, earth fault

Overload, idle running

Regulation and control

Sensorless current vector control (ISD)

Field-orientated control

Linear U/f characteristic curve

Setpoint input analog / PID input (option)

0 ... 10V,

10V, 0/4 ... 20mA

Analog setpoint resolution

10 bit based on measurement range

Analog output (optional)

0 ... 10V scalable

Setpoint consistency

Analog < 1%

Digital < 0.02% (option)

Motor temperature monitoring

I

2

t motor (UL/CUL certified), PTC / Bimetal switch (optional, not UL/CUL)

Ramp times

0 ... 99.99 s

Control outputs (optional)

1 or 2 relays 28V DC / 230V AC, 2A

Interface (optional)

According to option:

RS 485
RS 232

CANbus
CANopen
DeviceNet

Profibus DP
InterBus

AS interface

Inverter efficiency

approx. 95%

Ambient temperature

0℃ ... +50°C (S3 - 75% ED, 15 min.), 0°C ... +40°C (S1 - 100% ED)

> 22kW: only 0°C ... +40°C (S1 - 100% ED)

With UL/CUL certification, generally 0°C ...+40°C applies

Storage and transport temperature

-20°C ... +60/70°C, max. 85% humidity without condensation.

Long-term storage

See Section 8.6.1

Protection class

IP20

Electrical isolation

Control terminals (digital and analog inputs)

Max. mounting altitude above sea level

Up to 1000m: No power reduction

1000...4000m: 1%/ 100m power reduction (up to 2000m overvoltage cat. 3)

2000...4000m: Only overvoltage category 2 is maintained, external overvoltage protection at

the mains input is necessary

Wait time between two mains switch on cycles

60 sec for all devices in normal operating cycle