NORDAC SK 700E Operating Manual

20

Subject to technical alterations

BU 0700 GB-1411

2.10.7 Control unit connection

The manner and type of control unit connections are dependent on the options chosen (customer unit / special extension unit).
The possible variations are described in Chapter 3.2/3.3.

On these pages you will find general data and information on all customer units and special extension units.

Connection terminals:

- Plugs, terminals and connectors can be released with a small screwdriver

Maximum connection cross-section:

-

1.5 mm

2

or 1.0 mm

2

, depending on option

Cable:

-

Lay and shield separately from the mains/motor cables

Control voltages:

-

5V for the supply of an incremental encoder

(Short-circuit proof)

-

10V, max. 10mA, reference voltage for an external potentiometer

-

15V for the supply of the digital inputs or an incremental or absolute encoder

-

analog output 0 - 10V, max. 5mA for an external display unit

Note:

All control voltages are based on a common reference potential (GND).

5 / 15 V can if necessary, be taken from several terminals. The sum of the
currents is max. 300 mA.