7 control unit connection – NORD Drivesystems BU0700 User Manual
Page 20
NORDAC SK 700E Operating Manual
20
Subject to technical alterations
BU 0700 GB-1411
2.10.7 Control unit connection
The manner and type of control unit connections are dependent on the options chosen (customer unit / special extension unit).
The possible variations are described in Chapter 3.2/3.3.
On these pages you will find general data and information on all customer units and special extension units.
Connection terminals:
- Plugs, terminals and connectors can be released with a small screwdriver
Maximum connection cross-section:
-
1.5 mm
2
or 1.0 mm
2
, depending on option
Cable:
-
Lay and shield separately from the mains/motor cables
Control voltages:
-
5V for the supply of an incremental encoder
(Short-circuit proof)
-
10V, max. 10mA, reference voltage for an external potentiometer
-
15V for the supply of the digital inputs or an incremental or absolute encoder
-
analog output 0 - 10V, max. 5mA for an external display unit
Note:
All control voltages are based on a common reference potential (GND).
5 / 15 V can if necessary, be taken from several terminals. The sum of the
currents is max. 300 mA.