NORD Drivesystems BU0700 User Manual
Page 82
NORDAC SK 700E Operating Manual
82
Subject to technical alterations
BU 0700 GB-1411
List of the possible functions of the digital inputs P420 ... P425
Value Function
Description
Signal
0
No function
Input switched off.
---
1
Enable right
FI supplies output signal, rotation field right (if setpoint positive). 0
1 Flank (P428 = 0)
High
2
Enable left
FI supplies output signal, rotation field left (if setpoint positive). 0
1 Flank (P428 = 0)
High
If automatic start-up is active (P428 = 1), a high level is sufficient.
If the functions "Enabled right" and "Enabled left" are actuated simultaneously, the FI is blocked
3
Change rotation direction
Causes the rotation field to change direction (combined with
Enable right or left).
High
4
Fixed frequency 1
1
The frequency from P429 is added to the setpoint value.
High
5
Fixed frequency 2
1
The frequency from P430 is added to the setpoint value.
High
6
Fixed frequency 3
1
The frequency from P431 is added to the setpoint value.
High
7
Fixed frequency 4
1
The frequency from P432 is added to the setpoint value.
High
If several fixed frequencies are actuated at the same time, then they are added with the correct sign. In addition, the
analog setpoint (including minimum frequency) is added.
8
Parameter set switch Bit 0
Selection of the active Bit 0 parameter set (see P100)
High
9
Maintain the frequency
During the start-up or braking phase, a low level will cause the
output frequency to be "held". A high level allows the ramp to
proceed.
Low
10
Voltage disable
2
The FI output voltage is switched off and the motor runs freely to
a stop.
Low
11
Quick stop
2
The inverter reduces the frequency according to the programmed
emergency stop time (P426).
Low
12
Fault acknowledgement 2
Error acknowledgement with an external signal. If this function is
not programmed, an error can also be acknowledged by a low
enable setting.
01
Flank
13
PTC resistor input
2
Analog evaluation of the present signal switching threshold,
approx. 2.5 Volt. 2sec delayed E002 message.
Analog
14
Remote control
With Bus system control, low level switches the control to control
via control terminals.
High
15
Jog frequency
This frequency fixed value can be set using the HIGHER /
LOWER and ENTER keys.
High
16
Motor potentiometer
As setting value 09, is however not maintained below the
minimum frequency and above the maximum frequency.
Low
17
Parameter set switch Bit 1
Selection of the active parameter set Bit 2 (see P100).
High
18
Watchdog
2
Input must see a high flank cyclically (P460), otherwise error
E012 will cause a shutdown. Starting is with the first high flank.
01
Flank
19
Setpoint 1 on/off
Analog input switch-on and switch-off 1 (High = ON)
High
20
Setpoint 2 on/off
Analog input switch-on and switch-off 2 (High = ON)
High
21
Fixed frequency 5
1
The frequency from P433 is added to the setpoint.
High
22
Approach reference point
PosiCon option (see manual BU 0710)
High
23
Reference Point
PosiCon option (see manual BU 0710)
High
24
Teach-In
PosiCon option (see manual BU 0710)
High
25
Quit Teach-In
PosiCon option (see manual BU 0710)
High
These functions are only available with the PosiCon Special Extension Unit!
... continued on the next page