4 electrical data for ul/cul certification – NORD Drivesystems BU0700 User Manual
Page 117
BU 0700 GB-1411
Subject to technical alterations
117
7.4 Electrical data for UL/cUL certification
The data given in this section must be taken into account to comply with UL/CUL certification-
Use of mains fuses which are faster than those stated is permissible.
Size 1
Device type:
SK 700E ....
-151-340-A
-221-340-A
-301-340-A
-401-340-A
Nominal motor power
(4-pole standard motor)
380V
1½hp
2hp
3hp
4hp
460...480V
2hp
3hp
4hp
5hp
FLA
[A]
3.4
4.8
5.1
7.6
Permissible
mains fuse
J Class Fuse,
600V
10A
10A
15A
15A
Rec. mains fuse
Bussmann
LPJ-10SP
LPJ-10SP
LPJ-15SP
LPJ-15SP
Size 2 / 3
Device type:
SK 700E ...
-551-340-A
-751-340-A
-112-340-A
-152-340-A
Nominal motor power
(4-pole standard motor)
380V
5hp
7½hp
10hp
15hp
460...480V
7½hp
10hp
15hp
20hp
FLA
[A]
11
14
21
27
Permissible
mains fuse
J Class Fuse,
600V
20A
25A
35A
50A
Rec. mains fuse
Bussmann
LPJ-20SP
LPJ-25SP
LPJ-35SP
LPJ-50SP
Size 4
Device type:
SK 700E ...
-182-340-A
-222-340-A
Nominal motor power
(4-pole standard motor)
380V
20hp
25hp
460...480V
25hp
30hp
FLA
[A]
35
40
Permissible
mains fuse
J Class Fuse,
600V
50A
60A
Rec. mains fuse
Bussmann
LPJ-50SP
LPJ-60SP
Size 5 / 6
Device type:
SK 700E ....
-302-340-O
-372-340-O
-452-340-O
-552-340-O
Nominal motor power
(4-pole standard motor)
380V
30hp
40hp
50hp
60hp
460...480V
40hp
50hp
60hp
75hp
FLA
[A]
52
65
77
96
Permissible
mains fuse
J Class Fuse,
600V
80A
100A
125A
150A
Rec. mains fuse
Bussmann
FRS-R-80
FRS-R-100
FRS-R-125
FRS-R-150
Size 7
Device type:
SK 700E ....
-752-340-O
-902-340-O
Nominal motor power
(4-pole standard motor)
380V
75hp
100hp
460...480V
100hp
125hp
FLA
[A]
124
156
Permissible
mains fuse
J Class Fuse,
600V
200A
225A
Rec. mains fuse
Bussmann
FRS-R-200