NORD Drivesystems BU0700 User Manual
Page 116
NORDAC SK 700E Operating Manual
116
Subject to technical alterations
BU 0700 GB-1411
Size 4
Device type:
SK 700E ...
-182-340-A
-222-340-A
Nominal motor power
(4-pole standard motor)
400V
18.5kW
22.0kW
460...480V
25hp
30hp
Mains voltage
3 AC 380 - 480V, -20% / +10%, 47...63 Hz
Output voltage
3 AC 0 - Mains voltage
Nominal output current (rms)
[A]
35
45
Recommended braking
resistance
(Accessories)
22
Min. braking resistor
22
14
Typ. input current (rms)
[A]
50
60
Rec. mains fuse
slow-blowing
50A
63A
Type of ventilation
Fan cooling (temperature-controlled)
Weight
Approx. [kg]
12
12.5
Size 5 / 6
Device type:
SK 700E ....
-302-340-O
-372-340-O
-452-340-O
-552-340-O
Nominal motor power
(4-pole standard motor)
400V
30kW
37kW
45kW
55kW
460...480V
40hp
50hp
60hp
75hp
Mains voltage
3 AC 380 - 480V, -20% / +10%, 47...63 Hz
Output voltage
3 AC 0 - Mains voltage
Nominal output current (rms)
[A]
57
68
81
103
Recommended braking
resistance
(Acces-
sories)
12
8
Min. Brake resistor
9
6
Typ. input current (rms)
[A]
70
88
105
125
Rec. mains fuse
slow-blowing
100A
100A
125A
160A
Type of ventilation
Fan cooling
Weight
Approx. [kg]
24
28
Size 7 / 8
Device type:
SK 700E ....
-752-340-O
-902-340-O
-113-340-O
-133-340-O
-163-340-O-VT *
Nominal motor power
(4-pole standard motor)
400V
75kW
90kW
110kW
132kW
160kW
460...480V
100hp
125hp
150hp
180hp
220hp
Mains voltage
3 AC 380 - 480V, -20 % / +10 %, 47...63 Hz
Output voltage
3 AC 0 - Mains voltage
Nominal output current (rms)
[A]
133
158
193
230
280
Recommended braking
resistance
(Acces-
sories)
6
3
Min. braking resistance
5
3
Typ. input current (rms)
[A]
172
200
240
280
340
Rec. mains fuse
slow-blowing
200A
250A
300A
300A
400A
Type of ventilation
Fan cooling
Weight
Approx. [kg]
45
45
110
115
115
*) For equipment with reduced overload, see Chapter 7.1