7.2 Continuous thermal output
If the pulse frequency (P504) of the power end stage is increased, deviating from the standard settings, this will lead to a
reduction in continuous output power. The corresponding trend can be seen in the following diagram. The power loss is approx.
5% of the inverter nominal power (kW).
Diagram is valid
for 1.5...160kW devices
7.3 Electrical data
Size 1
Device type:
SK 700E ....
-151-340-A
-221-340-A
-301-340-A
-401-340-A
Nominal motor power
(4-pole standard motor)
400V
1.5kW
2.2kW
3.0kW
4.0kW
460...480V
2hp
3hp
4hp
5hp
Mains voltage
3 AC 380 - 480V, -20% / +10%, 47...63 Hz
Output voltage
3 AC 0 - Mains voltage
Nominal output current (rms)
[A]
3.6
5.2
6.9
9.0
Recommended braking
resistance
(Accessories)
200
100
Min. braking resistor
90
Typ. input current (rms)
[A]
6
8
11
13
Rec. mains fuse
slow-blowing
10A
10A
16A
16A
Type of ventilation
Convection
Fan cooling (temperature-controlled)
Weight
Approx. [kg]
4
Size 2 / 3
Device type:
SK 700E ...
-551-340-A
-751-340-A
-112-340-A
-152-340-A
Nominal motor power
(4-pole standard motor)
400V
5.5kW
7.5kW
11kW
15kW
460...480V
7½hp
10hp
15hp
20hp
Mains voltage
3 AC 380 - 480V, -20% / +10%, 47...63 Hz
Output voltage
3 AC 0 - Mains voltage
Nominal output current (rms)
[A]
11.5
15.5
23
30
Recommended braking
resistance
(Accessories)
60
30
Min. braking resistor
40
32
28
Typ. input current (rms)
[A]
17
21
30
40
Rec. mains fuse
slow-blowing
20A
25A
35A
50A
Type of ventilation
Fan cooling (temperature-controlled)
Weight
Approx. [kg]
5
9
9.5
0
20
40
60
80
100
120
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20
Cycle frequency [ kHz ]