(3) CUT OFF: output cut off at low fl ow rate (low fl ow cutoff function)

0.010m/s

Flow velocity

- 0.010m/s

Output

When fl ow rate is extremely low, its output can
be cut off. (range: 0 to 5.000 m/s or 16.4 ft/s)
If fl uid in the pipe is moving due to convec-
tion, etc., even though the valve is closed, this
fl owmeter outputs a measured value. There-
fore, values below an appropriate level should
be cut off.

[Operation]

(1) Press the

or

key on the OUTPUT CONTROL

screen and select “CUT OFF”. Then, press the

ENT

key, and the cursor moves to the set item. Output cut
off point is settable.

(2) Move the digit by pressing the

or

key and

enter a numeric value by pressing the

or

key.

After entry, press the

ENT

key.

Bulletin F-9-PUX2