(2) The screen to select analog input defi nition is displayed.

Select the kind of input and press the

ENT

key.

(2) “SETTING”: when setting the kind of analog input

Defi nition of Analog input1
NOT USED: Select this, when it is not used.

Current input (APPLICATION): Connect the external fl ow transmitter of 4 to 20mA DC.
Current input (FEEDING TEMP.): For using the Calorie mode, connect the feed-temperature 4 to

20mA DC.
When you set the defi nition of analog input2 to “CURRENT
INPUT (DIFFEREN TEMP.)”, “CURRENT INPUT (FEED-
ING TEMP.)” becomes invalid.

Voltage input: Connect the external fl ow transmission of 1 to 5V DC.

Defi nition of Analog input2

NOT USED: select this, when you do not use.
Current input (APPLICATION): Connect the external fl ow transmitter of 4 to 20mA DC.
Current input (RETURN TEMP.): For using the Calorie mode, connect the return-temperature 4 to

20mA DC.

Current input (DIFFEREN TEMP.): For using the Calorie mode, connect the FEEDING TEMP.

and the RETURN TEMP. of 4 to 20mA DC.

[Operation]

(1) Press the

ENT

key on the SETTING screen and the

cursor moves to “ANALOG INPUT/OUTPUT”.
Select “INPUT CH1 DEFINITION” or “INPUT CH2
DEFINITION” by the

or

key and press the

ENT

key.

INPUT CH1 DEFINITION

INPUT CH2 DEFINITION

Refer to “10.4 Setting of range” for setting of
input range.

CAUTION

Bulletin F-9-PUX2