(6) Move the digit by the

or

key and enter numeric

values by pressing the

or

key.

After entry, press the

ENT

key to set the range. The

full scale value will be set.

(7) Make settings for output limit high/low (upper/lower

limit for analog output).
Setting limit: Output limit low –20 to 0%

Output limit high 100 to 120%

Select “OUTPUT LIMIT LOW” by the

or

key.

Press the

ENT

key, and you are ready to set the output

limit low.

(8) Move the digit by the

or

key and enter numeric values by pressing the

or

key.

After entry, press the

ENT

key to set the range.

(9) Select “OUTPUT LIMIT LOW” by pressing the

or

key.

Set the output limit high in the same manner as the output limit low.

(3) Set the range type (single range or bi-directional

range).
Select “RANGE TYPE” by pressing the

or

key.

(4) Press the

ENT

key to display the RANGE TYPE

screen.
Select the range type by the

or

key and press

the

ENT

key.

(5) Set the full scale value for output range.

Setting range:
When the range kind is velocity or fl ow rate

0.000, ±0.300 to ±32.000m/s

(Flow velocity conversion)

When the range kind is thermal flow rate

0.000 to 9999999999

Select “FULL SCALE” by pressing the

or

key.

Press the

ENT

key, and you are ready to set the full scale.

Set RANGE so that fl ow rate to be measured exceeds 1.2 times its maximum value.
If measured value exceeds the set value, the status display on the measurement screen turns
“E4: RANGE OVER”.
Unless analog output is used, set the full scale setting at 0, and “E4: RANGE OVER” is not
displayed.

CAUTION

Bulletin F-9-PUX2