168

Total value display function: Display of forward or reverse total (reverse is displayed as minus)

Numeric value: 10 digits (decimal point is corresponding to 1 digit)
Unit: Metric/English system selectable
Metric system
Flow rate total: mL, L, m

3

, km

3

, Mm

3

, mBBL, BBL, kBBL

English system
Flow rate total: gal, kgal, ft

3

, kft

3

, Mft

3

, mBBL, BBL, kBBL, ACRE-ft

Consumed heat quantity (calorie) display function:

Display of consumed heating medium
Metric system
Heat fl ow: MJ/h, GJ/h
Total heat quantity: MJ, GJ
English system
Heat fl ow: MJ/h, GJ/h, BTU/h, kBTU/h, MBTU/h
Total heat quantity:

MJ, GJ, BTU, kBTU, MBTU

Computation function of consumed heat quantity (calorie):

This function calculates the heat quantity received and sent with liquid (water) in cooling
and heating.

Heat

source

Heat

exchanger

Converter

Converter

Temperature display function:

Fluid temperature be displayed by current input from temperature transmitter.
Metric system
Temperature unit: °C or K
English system
Temperature unit: F or K

Site data storage function: Max. 32 locations (sites) data (pipe size, material, fl uid type and etc) can be stored into

built-in non-volatile memory.

Damping:

0 to 100sec (every 0.1sec) confi gurable for analog output and velocity/fl ow rate display

Low fl ow cut:

Equivalent to 0 to 5m/s

Output setting function:

Current output scaling, output type, burnout setting and calibration

Serial communication function:

Instantaneous velocity, instantaneous fl ow rate, total value, heat fl ow, error information,
received waveform, analog input, velocity profi le data, logger data, etc. may be down-
loaded to personal computer.

Logger function:

Instantaneous velocity, instantaneous fl ow rate, total value, heat fl ow, error information,
received waveform, analog input, velocity profi le date can be saved in a SD memory
card.

Waveform display function: Bi-directional received waveforms may be displayed.
Graph display function:

Flow rate trend graph may be displayed.

Printing function (option):

Hard copy output of a screen
Periodic printing (type: text, graph)
Logger date (type: text, graph)

Flow velocity profi le measurement (option):

Flow velocity profi le may be observed in real time using the exclusive detector (option).

Bulletin F-9-PUX2

Consumed heat quantity
q = K · Q · (T1–T2)
K : heat quantity (calorie)
conversion factor(For heating K = 4.123,
For cooling = 4.186

Detector (PSX2)

Q: Flow rate of the fluid

T2: Fluid temperature (out)

T1: Fluid temperature (in)

Temperature sensor