(3) “Input CH1, CH2 Analog Input CALIBRATION”:

when adjusting zero and span for input signals

[Please prepare a current generator]

Calibration procedure

1) 10.3.2(1) set the “ANALOG INPUT/OUTPUT” to the “USE”
2) 10.3.2(2) set the defi nition of “SETTING” input CH to “CURRENT INPUT”.

[Operation]

(1) Move the cursor to the “INPUT” on the SETTING

screen by pressing the

or

key and display the

INPUT screen.
Press the

ENT

key, and the cursor moves to INPUT

CH1 or CH2.
Select “CH1: INPUT PROOFREADING” by the
or

key and press the

ENT

key.

Select the kind of input you set on the “SETTING”
screen by the

or

key and press the

ENT

key.

The cursor moves to “ADJUST”. Press the

ENT

key,

and you are ready to adjust input signals.

(2) Input 4 mA from external and move the cursor to “4

mA” by the

or

key. Then press the

ENT

key to

adjust zero.
Follow the procedures described in next page of input
calibration.

(3) Input 20 mA from external and move the cursor to

“20 mA” by the

or

key. Then press the

ENT

key to adjust span.
Follow the procedures described in next page of input
calibration.

Bulletin F-9-PUX2