Current Input Calibration procedure

ENT

Input 4mA from external.

Under calibration of 4mA

ENT

ENT

Input 20mA from external.

Under calibration of 20mA

End of calibration

After calibration, the “End of
Calibration” message appears
under the end of calibration button.

• Analog input has already been calibrated on the factory setting
• When you interrupt the calibration in the middle, the calibration value will be

lost.

If you interrupt the calibration, start from the beginning again.

• Calibrated analog input required for AI measurement.