Maple Systems HMI5000 Series User Manual
Page 117
Using EZware-5000
111
1010-1007, Rev. 10
b. Save file as *.emi for extended memory files.
You must use file names which correspond to the ten extended memory areas preconfigured in
the HMI (ex. em0.emi, em1.emi, …, em9.emi).
c. Save file as *.csv to open the file in applications such as Microsoft Excel.
12. Once the file is saved, you can copy the recipe file to your HMI by:
a. Procedure 1-- Downloading the file using the Project Manager:
i. With the computer connected to your HMI, click Transfer…Download.
ii. On the Download dialog box, check the RW enable box, then select the recipe file.
b. Procedure 2 -- Downloading using a SD card or USB Flash Drive:
i. Attach an SD card or USB Flash Drive to your computer.
ii. In Project Manager, click Build Download Data for CF/USB Disk button.
iii. Select the folder to save download data. Enter the SD card or USB Flash drive location.
iv. Check the Recipe (RW) enable box, then select the recipe file.
v. Click the Build button. A folder called ‘mt8000’ is created on the root directory of your
drive.
vi. Remove the SD or USB drive and connect it to your HMI.
If you are using more than one USB device, make sure that the USB Flash drive is connected first (this identifies the
USB Flash Drive as USB1).