beautypg.com

IAI America ERC User Manual

Page 125

background image

105

Default acceleration only MAX flag

To cause the actuator to decelerate gradually when stopping, a lower acceleration/deceleration should be set.
However, this will also reduce the acceleration.
This parameter allows for quick acceleration while reducing the deceleration.
However, the actual load must be one-third the rating or less.
Check the payload rating by referring to 1.3, “Specifications.”
The factory setting is “0: [Disable].”
When a target position is written to an unregistered position table, the setting in this parameter will be used as
the acceleration only MAX data for the applicable position number.
To enable the default value, change parameter No. 11 to “1: [Enable].”

Push & hold stop judgment period

This parameter is used as a judgment condition when determining if the load was contacted and the push & hold
operation has completed.
The push & hold operation is judged complete if the current-limiting value set in the position table has been
maintained for the period set in parameter No. 6.
Set an optimal value by considering the shape and strength of the load, as well as the current-limiting value.
The minimum setting unit is “1 [msec],” and the maximum judgment period is “255 [msec].” The factory setting is
“255 [msec].”
(Note) If the load has shifted and the current has changed during the push & hold judgment, the judgment

follows the timing chart shown below. This example assumes a judgment period of 255 msec.





















After reaching the push current, it is maintained for 200 msec. The current drops during the subsequent 20-msec
period, and accordingly the count is decremented by 20. Therefore, when the operation is resumed the count will
start from 180. Since the count will reach 255 after 75 msec at the push current, the controller will determine that
the push & hold operation has completed.
In this example, the total judgment period is 295 msec.

Current-limiting value at standstill during positioning

The factory setting conforms to the standard specification of the actuator.
Increasing this setting will increase the holding torque at standstill.
This setting need not be changed in normal conditions of use. However, to prevent hunting caused by large
external force applied while the actuator is at standstill, the value set in parameter No. 12 must be increased.
(Do not increase the value beyond 70%.)

Push current

20 msec

Start position

Target position

Counting starts

Counting continues until 200

Count is decremented to 180

Count is incremented to 255

Judgment of push & hold completion

75 msec