Delta 1.07 VFD-D D User Manual
Page 97
Chapter 4 Parameter Settings|DD Series
4-73
0001B:
1st
accel/decel.
0010B: 2nd accel/decel
0011B: 3rd accel/decel
0100B: 4th accel/decel
0101B: 5th accel/decel
0110B: 6th accel/decel
0111B: 7th accel/decel
1000B: 8th accel/decel
1001B: 9th accel/decel
1010B:
10th
accel/decel
1011B:
11th
accel/decel
1100B:
12th
accel/decel
1101B:
13th
accel/decel
1110B:
14th
accel/decel
1111B: 15th accel/decel
Bit12
1: enable bit06-11 function
Bit13~14
00B: No function
01B: operated by digital keypad
10B: operated by Pr.00-21 setting
11B: change operation source
Bit15
Reserved
2001H
Frequency
command
2002H Bit0
1: EF (external fault) on
Bit1
1:
Reset
Bit2
1: B.B. ON
Bit3~5
Reserved
Status monitor
Read only
2100H Error code: refer to Pr.06-16 to Pr.06-21
2119H
Bit0
Bit1
00: Stop
01: deceleration
Bit2
opening door is prohited,
Bit3
Bit4
00: CD command, OD output
01: CD command, OD output
10: OD command, CD output
11: Reserved
Bit5~7
Reserved
Bit8
1: Master frequency Controlled by communication
interface
Bit9
1: Master frequency controlled by analog/external
terminals signal
Bit10
1: Operation command controlled by communication
interface
Bit11
1: Parameters have been locked
Bit12
1: enable to copy parameter from keypad
Bit13~15
Reserved
2102H Frequency command (F)
2103H Output frequency (H)
2104H
Output
current (AXXX.X)
2105H
DC-BUS
Voltage (UXXX.X)
2106H
Output
voltage (EXXX.X)
2107H Current step number of Multi-Step Speed Operation
2116H Multi-function display (Pr.00-04)
2120H Frequency command when malfunction
2121H Output frequency when malfunction
2122H Output current when malfunction
2123H Motor frequency when malfunction
2124H Output voltage when malfunction
2125H DC-bus voltage when malfunction
2126H Output power when malfunction
2127H Output torque when malfunction
2128H
IGBT
Temperature of Power Module at Present Fault