Chapter 4 Parameter Settings|DD Series


4-24

4-2 Description of Parameter Settings

00 System Parameter

This parameter can be set during operation.

Identity Code of AC Motor Drive

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: Read only

Settings 0:200w

1:400w

Rated Current Display of AC Motor Drive

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: Read only

Settings 0:1.50A

2:2.50A

Pr. 00-00 displays the identity code of the AC motor drive. The capacity, rated current, rated voltage and

the max. carrier frequency relate to the identity code. Users can use the following table to check how the

rated current, rated voltage and max. carrier frequency of the AC motor drive corresponds to the identity

code.

Pr.00-01 displays the rated current of the AC motor drive. By reading this parameter the user can check if

the AC motor drive is correct.

Parameter Reset

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0

Settings 0: No function

1: Parameters locked

8: Keypad locked

10: All parameters are reset to factory setting (33.3Hz, 230V)

When it is set to 1, all parameters are read only except Pr.00-00~00-07 and it can be used with password

setting for password protection.

When Pr.00-02=10, all parameters are reset to factory setting. If password lock was used, please unlock

first. After Pr.00-02 set to 10, password will also be cleared and reset to factory setting.

When Pr.00-02=08, the digital keypad will be locked and only Pr.00-02, Pr.00-07 can be set.

Start-up Display Selection

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0

Settings 0: Display the frequency command value (F)

1: Display the actual output frequency (H)

2: Display the content of user-defined unit (U)

3: Display the output current (A)

This parameter determines the start-up display page after power is applied to the drive.

Content of Multi Function Display

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 2

Settings 0: Display output current (A )

1: Display actual frequency (Hz)

2: Display DC-BUS voltage ( U)

3: Display output voltage( E )

4: Display power factor angle (n.)