Door Close DC Brake Starting Frequency

Control mode VF

VFPG

SVC

FOCPG

Factory setting: 0.00

Settings 0.00~120.00Hz

During the period AC motor drive decelerating to stop, this parameter sets the DC brake starting

frequency If Pr.05-24 is lower than Pr.01-09 (starting frequency), DC brake will regards lowest frequency

as starting frequency.

Door Re-open Current Level 1

Control mode VF

VFPG

SVC

FOCPG

FOCPM

VF

Factory setting: 100.0

Settings 0.0~150.0% (AC drive’s rated current)

Door Re-open Current Level 1 for Acceleration Area

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 150

Settings 100~200% (100% is Pr.05-25 setting)

Door Re-open Current Level 1 for Low Speed Area

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 100.0

Settings 0.0~150.0%(Drive’s rated current)

Pr.05-25~05-27 is setting for door open/close curve set 1. When one of MI (Pr.02-01~02-05) is set to 25,

door open/close curve switch to 2nd set.

Door Re-open Current Level 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 100.0

Settings 0.0~150.0%(Drive’s rated current)

Door Re-open Current Level 2 for Acceleration Area

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 150

Settings 0.0~150.0% (Drive’s rated current)

Door Re-open Current Level 2 for Low Speed Area

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 100

Settings 100~200%(100% is the setting in Pr.05-29)

Pr.05-28~05-30 is setting for door open/close curve set 2. When one of MI (Pr.02-01~02-05) is set to 25,

door open/close curve switch to 2nd set.

Door Re-open Low Speed Boundary

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 2.0

Settings

1.0~99.0%(Total door width=100%; range between 0%~Pr.05.31 is excluded from low
speed detection area)

Door Re-open Acceleration Boundary

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 70.0

Settings

8.0~97.0% (Total door width =100%; range between Pr.05.32~100% is the
acceleration area)

During the door close, it will re-close from the open complete position to the close complete position

when there is an obstacle (the stall current exceeds Pr. 05.25/05.26/05.28/05.29). Door close command

will be ignored when the drive is perform re-opening and will be valid again after door completely open is

reached.

Pr.05-33 sets the time for decelerating to 0 Hz when door close error occurs. It is recommended to set a

minimum value less than the current limit in order for door to re-open in shortest time to ensure

passenger’s safety.