Delta 1.07 VFD-D D User Manual
Page 63
Chapter 4 Parameter Settings|DD Series
4-39
8: 1st, 2nd acceleration/deceleration time selection
○
○
○
○
○
9: Force stop (NO) input
○
○
○
○
○
10: Demo mode
○
○
○
○
○
11: Emergency stop (NO) input
○
○
○
○
○
12: Source of operation command (Keypad/External terminals) ○
○
○
○
○
13: Parameter lock enable (NC)
○
○
○
○
○
14: Door open complete signal
○
○
○
○
○
15: Door close complete signal
○
○
○
○
○
16: Door open speed switch signal
○
○
○
○
○
17: Door close speed switch signal
○
○
○
○
○
18: Open allowance signal
○
○
○
○
○
19: Screen signal input
○
○
○
○
○
20: Door curve signal input for 2nd set door open/close
○
○
○
○
○
21: Reset signal input
○
○
○
○
○
22: Input system security circuit confirmation signal (DCC)
○
○
○
○
○
23: Input enforced door closing signal (NUD)
○
○
○
○
○
This parameter selects the functions for each multi-function terminal.
Summary of Function Settings:
Settings
Functions
Descriptions
0
No function
Any unused terminals should be programmed to 0 to insure they
have no effect on operation.
1
Multi-step speed command 1
2
Multi-step speed command 2
3
Multi-step speed command 3
4
Multi-step speed command 4
When door control mode (Pr.00-09)is set 2 (multi-step speed
control), these four inputs can be used for 16 step speed
frequencies
5
Fault reset
Reset drive setting after fault is cleared.
6
Low speed operation
Before using this function, please make sure that AC motor drive is
stop. At this moment, key “STOP” on the digital keypad is still valid.
When this contact is OFF, motor will stop by deceleration time of
low speed operation.
7
OD/CD command for low
speed operation
ON: open the door (OD)
OFF: closer the door (CD)
This command will be effective only when external terminal for low
speed operation is active.
8
1st, 2nd
acceleration/deceleration
time selection
When signal is input, the AC motor drive can switch between 1st
and 2nd acceleration/deceleration time
9
Force stop (NO) input
This parameter has the same function as the “STOP” command
and no error message will be displayed. It does not require a
RESET but a new RUN command is needed for the drive to run
again.
10
Demo mode
When this setting is enabled, the output frequency of AC motor
drive will run by open/close curve repeatedly till this setting is
disabled. It will get the best open/close curve by this action.
11
Emergency stop (NO) input When setting to 11, the Multi-Function Input Terminal can be used
to stop the AC motor drive in case of malfunction in the application.
It will display “EF”. Please “RESET” after the fault has been
cleared.
12
Source of operation
command (Keypad/External
terminals)
ON: Operation command via Ext. Terminals
OFF: Operation command via Keypad
Pr.00-14 is disabled if this parameter is set to 13.
13
Parameter lock enable (NC) When this setting is enabled, all parameter reading value will be
00. This setting must be disabled in order to read the parameter
content.