04 door open parameters – Delta 1.07 VFD-D D User Manual
Page 71
Chapter 4 Parameter Settings|DD Series
4-47
04 Door Open Parameters
This parameter can be set during operation.
Door Open by Initial Speed
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 2.00
Settings 0.00~120.0Hz
Door Open Distance by Initial Speed
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 300
Settings 0~65535 (pulses number)
Door Open Time by Initial Speed
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 1.0
Settings 0~20.0s
Door Open High Speed 1
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 15.00
Settings 0.00~120.0Hz
Door Open by Final Speed Begins
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 90.0
Settings 0.0~100.0% (Door width setting in %)
Door Open Final Speed
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 5.00
Settings 0.00~120.0Hz
Door Open by Holding Speed Begins
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 95.0
Settings 0.0~100.0% (Door width setting in %)
Door Open Holding Speed
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 2.00
Settings 0.00~120.0Hz
Door Open Acceleration Time 1
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 1.0
Settings 0.1~3600sec
Door Open Deceleration Time 1
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 1.0
Settings 0.1~3600sec
Door Open Holding Torque Level
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 50.0
Settings 0.0~150.0% (AC drive’s rated current)
Door open distance (Pr.04-01) is set in pulses number but when converting into %; it must be smaller
than the setting in Pr.04-04. Door close completely is 0% and door open completely is 100%.
Please refer to the diagram below and adjust door open/close curve to your requirement.