Chapter 4 Parameter Settings|DD Series


4-47

04 Door Open Parameters

This parameter can be set during operation.

Door Open by Initial Speed

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 2.00

Settings 0.00~120.0Hz

Door Open Distance by Initial Speed

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 300

Settings 0~65535 (pulses number)

Door Open Time by Initial Speed

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 1.0

Settings 0~20.0s

Door Open High Speed 1

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 15.00

Settings 0.00~120.0Hz

Door Open by Final Speed Begins

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 90.0

Settings 0.0~100.0% (Door width setting in %)

Door Open Final Speed

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 5.00

Settings 0.00~120.0Hz

Door Open by Holding Speed Begins

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 95.0

Settings 0.0~100.0% (Door width setting in %)

Door Open Holding Speed

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 2.00

Settings 0.00~120.0Hz

Door Open Acceleration Time 1

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 1.0

Settings 0.1~3600sec

Door Open Deceleration Time 1

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 1.0

Settings 0.1~3600sec

Door Open Holding Torque Level

Control mode VF VFPG SVC FOCPG FOCPM

Factory setting: 50.0

Settings 0.0~150.0% (AC drive’s rated current)

Door open distance (Pr.04-01) is set in pulses number but when converting into %; it must be smaller

than the setting in Pr.04-04. Door close completely is 0% and door open completely is 100%.

Please refer to the diagram below and adjust door open/close curve to your requirement.