Door open holding torque, Response time of door open holding torque, Door open high speed 2 – Delta 1.07 VFD-D D User Manual
Page 72: Door open acceleration time 2, Door open deceleration time 2, Door open holding torque 2, Door open time-out setting, Holding time for od (open door)terminal
Chapter 4 Parameter Settings|DD Series
4-48
Door Close
Holding Speed
Open Door (R EV)
Door Open Limi t
0.0%
100.0%
Close Door (FWD)
04.00
Door Open
Speed
by Ini tial
04.08
Door Open
Acceleration
Time 1
04.09
Door Open
Deceleration
Time 1
04.03
Door Open H igh Speed 1
04.05
Door Open
Final Speed
04.01
Door Open D istance
by Ini tial Speed
04.04
Door Open
Final Speed
by
Begi ns
04.06
Door Open
by Holding
Speed Begins
04.07
Door Open
Holding Speed
05.03
Door Close
High Speed 1
D oor Close
Accel er ation Time 1
05.05
05.04
05.06
by
Door Close
Holding
Speed
Begins
05.07
05.09
05.01
Door Close
Distance by
Ini tial Speed
05.00
Door Close
Ini tial Speed
Door Close Limit
Door Close
Final Speed
Door Close
Final Speed
Door Close
by Final Speed
Begi ns
05.08
Door Open Holding Torque
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 20.0
Settings 0.0~100.0% (AC drive’s rated current)
Response Time of Door Open Holding Torque
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.20
Settings 0.01~10.00sec
When the door is in the open complete position, it needs holding torque to keep the door still in complete
position. To prevent motor overload, holding torque should be set within a limit.
Door Open High Speed 2
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 30.00
Settings 0.00~400.0Hz
Door Open Acceleration Time 2
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 1.0
Settings 0.1~3600sec
Door Open Deceleration Time 2
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 1.0
Settings 0.1~3600sec
Door Open Holding Torque 2
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~150.0% (AC drive’s rated current)
Door Open Time-out Setting
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~180.0sec (0.0 sec: Disable)
Holding Time for OD (Open Door)Terminal
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~999.9sec (999.9 sec for always holding)
This parameter is used to clear the OD terminal signal (door open signal) when door open complete.
During the holding period, AC Motor Drive will still be in RUN status. After holding time, AC Motor Drive
will STOP. The holding time is valid only when door open has reached the complete position.