Delta 1.07 VFD-D D User Manual
Page 41
Chapter 4 Parameter Settings|DD Series
4-17
Parameter
Explanation
Settings
Factory
Setting VF VFP SVC FO
C
FO
C
52:Password error (PcodE)
0
○ ○ ○ ○ ○
53:Software error (ccodE)
0
○ ○ ○ ○ ○
54:Communication time-out (cE1)
0
○ ○ ○ ○ ○
55: Communication time-out (cE2)
0
○ ○ ○ ○ ○
56: Communication time-out (cE3)
0
○ ○ ○ ○ ○
57: Communication time-out (cE4)
0
○ ○ ○ ○ ○
58 Communication time-out (cE10)
0
○ ○ ○ ○ ○
59:PU time-out (cP10)
0
○ ○ ○ ○ ○
60: Brake chopper error (bF)
0
○ ○ ○ ○ ○
61~67: Reserved
0
○ ○ ○ ○ ○
68: Door open/close complete signal
error
0
○ ○ ○ ○ ○
69:Door open time-out (DOT)
0
○ ○ ○ ○ ○
06.23 Electronic Thermal
Overload Relay Selection
0: Special motor for AC drive
1: Standard motor
2: Disable
2
06.24 Electronic Thermal
Characteristic
30.0~600.0sec 60.0
○ ○ ○ ○ ○
06.25 Auto Restart After Fault
0~10 0
○ ○ ○ ○ ○
06.26 Auto Reset Time for Restart
after Fault
0.1~600.0 60.0
○ ○ ○ ○ ○
06.27 Over-torque Detection
Selection (OT1)
0: disable
1: over-torque detection during constant
speed operation, continue to operate
after detection
2: over-torque detection during constant
speed operation, stop operation after
detection
3: over-torque detection during
operation, continue to operate after
detection
4: over-torque detection during
operation, stop operation after detection
0
○ ○ ○ ○ ○
06.28 Over-torque Detection Level
(OT1)
10~250% 150
○ ○ ○ ○ ○
06.29 Over-torque Detection Time
(OT1)
0.0~60.0 sec
0.1 ○ ○ ○ ○ ○