Chapter 4 Parameter Settings|DD Series


4-40

14

Door open complete signal When Pr.06-11 is set to 01 or 03, drive will open the door to the

completed position by this signal.

15

Door close complete signal When Pr.06-11 is set to 02 or 03, drive will close the door to the

completed position by this signal.

16

Door open speed switch
signal

When door control mode (pr.00-09) is set to 3 speed control mode,

this terminal can be used for switching speed.

17

Door close speed switch
signal

When door control mode (pr.00-09) is set to 3 speed control mode,
this terminal can be used for switching speed.

18

Open allowance signal

When this setting is enabled, it allows opening the door. It also can
be used for the signal of door zone.

19

Screen signal input

20

Door curve signal input for
2nd step door open/close

When this setting is ON, it will run the curve of 2nd step door
open/close.

21

Reset signal input

When parameter is set to 21, the drive re-positioning begins.

22

Input system security circuit
confirmation signal (DCC)

When the motor drive receives this signal then any door closing
signal will not be input. And the door will remain at the actuation
position

23

Input enforced door closing
signal (NUD)

When the motor drive receives this signal, it will close at low speed
(Pr03-10), but does not respond to stop closing door function.

Digital Terminal Input Debouncing Time (MD-5-13)

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.005

Settings 0.001~30.000sec

This parameter is to delay the signals on digital input terminals. 1 unit is 2.5 msec. The delay time is to

debounce noisy signals that could cause the digital terminals to malfunction but response time maybe a

bit slower.

Digital Input Operation Direction

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 60

Settings 0~65535

This parameter is used to set the input signal level.

bit 0 is CD terminal, bit 1is OD terminal and bit 2~bit 6 areMI1~MI5。

User can change the terminal status ON/OFF by communicating.

For example, MI1 is set to 1 (multi-step speed command 1), MI2 is set to 2 (multi-step speed command

2). Then the forward + 2nd step speed command=1001(binary) =9 (Decimal). Only need to set

Pr.02-07=9 by communication and it can forward with 2nd step speed. It doesn’t need to wire any

multi-function terminal.

bit6 bit5 bit4

bit3 bit2 bit1

bit0

MI5 MI4 MI3

MI2 MI1 OD

CD

Multi-function Output (Relay1)

Factory setting: 16

Multi-function Output (Relay2)

Factory setting: 17

Multi-function Output (MO1)

Factory setting: 0

Multi-function Output (MO2)

Factory setting: 0