beautypg.com

Delta 1.07 VFD-D D User Manual

Page 58

background image

Chapter 4 Parameter Settings|DD Series


4-34

NOTE

;

In torque/vector control mode, it is not recommended to have motors run in parallel.

;

It is not recommended to use torque/vector control mode if motor rated power exceeds the

rated power of the AC motor drive.

;

The no-load current is usually 20~50% X rated current.

;

The rated speed can not be greater than or equal to 120f/p (f=rated frequency Pr.01-32; P:

number of motor poles Pr.01-15).

Full-load Current of Motor (IM)

Control mode VF

VFPG

SVC

FOCPG

Unit: Amper
Factory setting: 1.00

Settings (20~120%)*00.01

Amps

This value should be set according to the rated frequency of the motor as indicated on the motor

nameplate. The factory setting is 90% X rated current.

Example: If rated current for 400W model is 2.5A. The current range for user will be 0.5~3.0A.

(2.5*20%=0.5 2.5*120%=3.0)

Rated power of Motor (IM)

Control mode

SVC

FOCPG

Factory setting: 0.06

Settings 0.00~655.35

kW

This parameter sets motor’s rated power. Factory setting will be the drive’s power.

Rated speed of IM Motor (rpm)

Control mode

VFPG

SVC

FOCPG

Factory setting: 250

Settings 0~65535

This parameter sets motor’s rated speed and it must be set according to the specification shown on the

nameplate.

Number of Motor Poles (IM)

Control mode VF

VFPG

SVC

FOCPG

Factory setting: 16

Settings 2~96

This parameter sets number of motor poles (odd value is invalid).

No-load Current of Motor (IM)

Control mode

VFPG

SVC

FOCPG

Factory setting: #. ##

Settings 00~ Pr.01.12 factory setting

Factory setting of the drive’s rated current is 40%.

Rs of Motor (IM)

Control mode

SVC

FOCPG

Factory setting: 0.000

Settings 0.000~65.535

Ω

Rr of Motor (IM)

Control mode

SVC

FOCPG

Factory setting: 0.000

Settings 0.0~65.535

Ω

Lm of Motor (IM)

Control mode

SVC

FOCPG

Factory setting: 0.0

Settings 0.0~6553.5mH

Lx of Motor (IM)

Control mode

SVC

FOCPG

Factory setting: 0.0