Output voltage 3, Output frequency 4, Output voltage 4 – Delta 1.07 VFD-D D User Manual
Page 61
Chapter 4 Parameter Settings|DD Series
4-37
Settings 0.00~120.00Hz
Output Voltage 3
Control mode VF
VFPG
Factory setting: 5.0
Settings 0.0V~240.0V
Output Frequency 4
Control mode VF
VFPG
SVC
FOCPG
Factory setting: 0.00
Settings 0.00~120.00Hz
Output Voltage 4
Control mode VF
VFPG
Factory setting: 0.0
Settings 0.0V~240.0V
V/f curve setting is usually set by the motor’s allowable loading characteristics. Pay special attention to
the motor’s heat dissipation, dynamic balance, and bearing lubricity, if the loading characteristics exceed
the loading limit of the motor.
The frequency setting of V/F curve must be set according to this rule, Pr. 01.32
≥01.34≥01.36≥01.38.
There is no limit for the voltage setting, but a high voltage at low frequency may cause motor damage,
overheat, and stall prevention or over-current protection. Therefore, please use the low voltage at the low
frequency to prevent motor damage.