Chapter 4 Parameter Settings|DD Series


4-58

1.

Incorrect door close limit:
a. The signal for the door open limit is received before Pr.05-04 setting.
b. The signal for the door open limit isn’t received after Pr.05-06setting.


2. Incorrect door open limit:

a. The signal for the door close limit is received before Pr.04-04 setting.
b. The signal for the door close limit isn’t received after Pr.04-06 setting.

When bit 1=1, the drive will not re-open the door when it detects a door closing torque higher than

Pr.05-25 (05-28).

When bit 3=1 and the drive is in torque holding status after door open completely, the door width is

auto-reset to 100.0%.

Position Control Mode

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0

Settings 0: No limit signal, detect by PG number and current level.

1: Door open limit signal only, door close by PG number or current level detection.

2: Door close limit signal only,door open by PG number or current level detection.

3: Door open and close limit signal

4: Detect by PG number and also accept external door open/close limit signal

5: No limit signal, detect by PG number and current level. (For Pr.00-09=3 speed
control mode)

When Pr.06-11 setting is 1 to 5 and Pr. 06-12 is NOT set to 0, the AC drive will regard this setting as

open/close complete position if following two conditions are met:

A. It has open/close limit signal.

B. When the stall current level exceeds Pr.06-12.

When this parameter is set to 0 “No limit signal”, the door open/close complete position can be check by

following two methods:.

A. When Pr. 06-12 is set to 0: When PG feedback frequency is almost 0 due to motor stall, it is regarded

as open/close complete position.

B. When Pr. 06-12 is NOT set to 0: When current exceeds this level due to motor stall, it is regarded as

open/close complete position.

NOTE

1. It is recommended to use method B for the transmission mechanism skids easily.

2. This function works in distance control mode only. For multi-step control mode, please use door

open/close limit signal to verify if door reaches its open/close complete position.

Stall Current Level of Position Mode

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 30.0

Settings 0.0~200.0% (AC drive’s rated current)

This parameter sets the stall current level for open/close complete position and is to be used with

Pr.06-11.

Door Open/Close Holding Time Before Next Demo

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 2.0

Settings 0.0~99.99sec

During demonstration in demo mode, this parameter sets the door holding time before it goes on to the

next demonstration.