14 environmental condition – Delta 1.07 VFD-D D User Manual
Page 120
Chapter 5 Troubleshooting |DD Series
5-15
5.14 Environmental Condition
Since AC motor drive is an electronic device, you should comply with the environmental condition stated
in the appendix A. Following are the remedial measures for necessary.
1.
To prevent vibration, anti-vibration spacer is the last choice. The vibration tolerance must
be within the specification. The vibration effect is equal to the mechanical stress and it
cannot occur frequently, continuously or repeatedly to prevent damaging AC motor drive.
2.
Store in a clean and dry location free from corrosive fumes/dust to prevent rustiness,
poor contact. It also may cause short by low insulation in a humid location. The solution
is to use both paint and dust-proof. For particular occasion, use the enclosure with
whole-seal structure.
3. The surrounding temperature should be within the specification. Too high or low
temperature will affect the lifetime and reliability. For semiconductor components,
damage will occur once any specification is out of range. Therefore, it is necessary to
clean and periodical check for the air cleaner and cooling fan besides having cooler and
sunshade. In additional, the microcomputer may not work in extreme low temperature
and needs to have heater.
4.
Store within a relative humidity range of 0% to 90% and non-condensing environment.
Do not turn off the air conditioner and have exsiccator for it.