Chapter 1 Introduction |DD Series

1-4

1-2 Preparation for Installation and Wiring

Install the AC motor drive in an environment with the following conditions:

Air Temperature:

-10 ~ +45°C (14 ~ 113°F)

Relative Humidity:

<90%, no condensation allowed

Atmosphere pressure: 86 ~ 106 kPa
Installation Site
Altitude:

<1000m

Operation

Vibration:

<20Hz: 9.80 m/s

2

(1G) max

20 ~ 50Hz: 5.88 m/s

2

(0.6G) max

Temperature:

-20°C ~ +60°C (-4°F ~ 140°F)

Relative Humidity:

<90%, no condensation allowed

Atmosphere pressure: 86 ~ 106 kPa

Storage

Transportation

Vibration:

<20Hz: 9.80 m/s

2

(1G) max

20 ~ 50Hz: 5.88 m/s

2

(0.6G) max

Pollution Degree

2: can be used in a factory type environment.

Minimum Mounting Clearances

;

The drive installation can be on a platform or on the wall. The left and middle figures show the

drive installation on a platform from the front and the side-view. The right figure shows wall
mounting. Both platform mounting and wall mounting are required to keep minimum mounting
clearances for good ventilation.

A B C D

20mm 15mm 20mm 8mm