Chapter 4 Parameter Settings|DD Series


4-66

09 Communication Parameters

This parameter can be set during operation.

RS-485

Seri al interface

1: +E V
2

: SG +

5: NC
6: NC

: G ND

3: SG -
4

6 1

When the AC motor driv e is controlled by RS- 485 seri al
communication,a c onv er ter, VFD-USB 01 or IF D8500,

should be connected between the AC motor driv e and P C.

Communication Address

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 1

Settings 01~254

If the AC motor drive is controlled by RS-485 serial communication, the communication address for this

drive must be set via this parameter. And the communication address for each AC motor drive must be

different and unique.

Transmission Speed

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 19.2

Settings 4.8~115.2Kbps

This parameter is used to set the transmission speed between the RS485 master (PLC, PC, etc.) and AC

motor drive. RS-485 communication can also be used to change the drive’s parameter and control the

drive’s operation status.

Transmission Fault Treatment

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 3

Settings Warn and keep operating

Warn and RAMP to stop

Reserved

No action and no display

This parameter is used to set the reaction to transmission errors occur.

Time-out Detection

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.0

Settings 0.0~100.0sec

This parameter is used to set the duration of communication and keypad time-out.

Communication Protocol

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 13

Settings 0: 7N1 (ASCII)

1: 7N2 (ASCII)

2: 7E1 (ASCII)

3: 7O1 (ASCII)

4: 7E2 (ASCII)

5: 7O2 (ASCII)

6: 8N1 (ASCII)

7: 8N2 (ASCII)

8: 8E1 (ASCII)

9: 8O1 (ASCII)

10: 8E2 (ASCII)

11: 8O2 (ASCII)

12: 8N1 (RTU)

13: 8N2 (RTU)