Chapter 2 Wiring|DD Series

2-3

Wiring/Terminals Setting

Used with internal power (+24Vdc)

Used with external power

COM

MI1

+24V

MI2

MI5

~

External +24V power

+

COM

MI1

+24V

MI2

MI5

~

COM

CAUTION!

; The wiring of main circuit and control circuit should be separated to prevent erroneous actions.
; Please use shield wire for the control wiring and not to expose the peeled-off net in front of the

terminal.

; Please use the shield wire or tube for the power wiring and ground the two ends of the shield wire

or tube.

; Damaged insulation of wiring may cause personal injury or damage to circuits/equipment if it

comes in contact with high voltage.

; The AC motor drive, motor and wiring may cause interference. To prevent the equipment damage,

please take care of the erroneous actions of the surrounding sensors and the equipment.

; When the AC drive output terminals U/T1, V/T2, and W/T3 are connected to the motor terminals

U/T1, V/T2, and W/T3, respectively. To permanently reverse the direction of motor rotation, switch
over any of the two motor leads.

; With long motor cables, high capacitive switching current peaks can cause over-current, high

leakage current or lower current readout accuracy. For usage of long motor cables use an AC
output reactor.

; The AC motor drive, electric welding machine and the greater horsepower motor should be

grounded separately.

; Use ground leads that comply with local regulations and keep them as short as possible.
; No braking resistor is built in the VFD-DD series, it can install braking resistor for those occasions

that use higher load inertia or frequent start/stop. Refer to Appendix B for details.

; Multiple VFD-DD units can be installed in one location. All the units should be grounded directly to

a common ground terminal, as shown in the figure below. Ensure there are no ground loops.

; The wiring of main circuit and control circuit should be separated to prevent

erroneous actions.

; Please use shield wire for the control wiring and not to expose the peeled-off

net in front of the terminal.

; Please use the shield wire or tube for the power wiring and ground the two

ends of the shield wire or tube.