Chapter 4 Parameter Settings|DD Series


4-14

06 Protection and Special Parameters

This parameter can be set during operation.

Parameter

Explanation

Settings

Factory

Setting VF VFP SVC FO

C

FO

C

06.00 Software Braking Level

350.0~450.0Vdc 380.0

○ ○ ○ ○ ○

06.01 ED Setting of Brake

Resistor

0~100% 50

○ ○ ○ ○ ○

06.02 Current Boundary

0~250%

200 ○ ○

06.03 Forward Motor Torque Limit 0~250%

200 ○ ○

06.04 Forward Regenerative

Torque Limit

0~250%

200 ○ ○

06.05 Reverse Motor Torque Limit 0~250%

200 ○ ○

06.06 Reverse Regenerative

Torque Limit

0~250%

200 ○ ○

06.07 Emergency/Force Stop

Deceleration Method

0:Coast to stop
1: Decelerate by 1st decel. time
2: Decelerate by 2nd decel. time
3:By Pr.05.33 setting

3

○ ○ ○ ○ ○

06.08 Low Voltage Level

160.0~270.0Vdc 180.0

○ ○ ○ ○ ○

06.09 High Temperature

Overheat Warning (OH)

0.0~110.0℃

85.0 ○ ○ ○ ○ ○

06.10

Action after door
re-open/re-close

Bit 0=0:Not detecting incorrect

open/close limit

Bit 0=1:Detects incorrect open/close

limit

Bit 1=0:Door re-open when door close

error occur

Bit 1=1:Door will not re-open when door

close error occur

Bit 2=0:Enable S-Curve when door

re-open

Bit 2=1:Disable S-Curve when door

re-open

Bit 3=0: When door open complete, will

not reset door position to
100.0%.

Bit 3=1:When door open complete,

resets door position to 100.0%

Bit4=0 Door opening in position not

supported, limited signal will be
output after the torque is
enabled.

Bit4=1 Door opening in position is

supported, limited signal will be
output after the torque is
enabled.

Bit5=0 Reset LVn error automatically,

MO terminal sends error signal

Bit5=1 Reset LVn error

automatically, MO terminal
sends error signal

2

○ ○ ○ ○ ○