Delta 1.07 VFD-D D User Manual
Page 81
Chapter 4 Parameter Settings|DD Series
4-57
Emergency/Force Stop Deceleration Method
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 3
Settings 0:Coast to stop
1: Decelerate by 1st decel. time
2: Decelerate by 2nd decel. time
3:By Pr.05.33 setting
When multi-function input terminal (MI) is set to 09 or 11, this parameter is active and the drive will
operate as the setting in Pr.06-07.
Low Voltage Level
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 180.0
Settings 160.0~270.0Vdc
High Temperature Overheat Warning (OH)
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 85.0
Settings 0.0~110.0℃
Action after door re-open/re-close
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 2
Settings Bit0=0: Disable to detect the incorrect open/close limit function
Bit0=1: Enable to detect the incorrect open/close limit function
Bit1=0: Enable to re-open when door close error
Bit1=1: Disable to re-open when door close error
Bit2=0: Enable S-Curve when re-open
Bit2=1: Disable S-Curve when re-open
Bit3=0: Disable to reset door width to 100.0% after door open completed
Bit3=1: Enable to reset door width to 100.0% after door open completed
When Bit 0=1, if the drive is in distance control mode, it is able to detect the door open/close error; in
addition, when MO(multi-function output terminal) is set to 8, the drive will output door open/close error
warning.
In Distance Control Mode, the detection method for the incorrect door open/close limit is shown as
follows.
04-04
Door Open Final
by Speed Begins
04-06
Door Open
by Holding
Speed Begins
Door Open Limit
100.0%
05-04
Door Close
by Final Speed
Begins
05-06
Door Close
by Holding
Speed Begins
Door Close Limit
0.0%
Open(REV)
Close(FWD)
No signal
for the door
close limit
The signal for the door close limit is received
The signal for the door open limit is received
No signal
for door
open limit