Delta 1.07 VFD-D D User Manual
Page 60
Chapter 4 Parameter Settings|DD Series
4-36
Settings 0~10000 (0: No action)
The motor will have current wave motion in some specific area. It can improve this situation by setting
this parameter. (When it is high frequency or run with PG, it can be set to 0. when the current wave
motion happens in the low frequency, please increase the value in Pr.01-28.)
Accumulative Motor Operation Time (Min.)
Control mode VF
VFPG
SVC
FOCPG
Factory setting: 0
Settings 0~1439
Accumulative Motor Operation Time (day)
Control mode VF
VFPG
SVC
FOCPG
Factory setting: 0
Settings 0~65535
This parameter records the motor running time. When Pr.01-29 and Pr.01-30 are set to 00, it clears the
setting to 0. Operation time will not be recorded if it is shorter than 60 sec.
Maximum Output Frequency
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 50
Settings 10.00~120.00Hz
This parameter determines the AC motor drive’s Maximum Output Frequency. All the AC motor drive
frequency command sources (analog inputs 0 to +10V, 4 to 20mA, 0 to 20mAand ±10V) are scaled to
correspond to the output frequency range.
Output Frequency 1(Base frequency /Motor rated frequency)
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 50
Settings 0.00~120.00Hz
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. If the motor is 60Hz, the setting should be 60Hz. If the motor is 50Hz, it should be set to
50Hz.
Output Voltage 1(Base voltage/Motor rated voltage)
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 220.0
Settings 0.0V~240.0V
This value should be set according to the rated voltage of the motor as indicated on the motor nameplate.
If the motor is 220V, the setting should be 220.0. If the motor is 200V, it should be set to 200.0.
There are many motor types in the market and the power system for each country is also difference. The
economic and convenience method to solve this problem is to install the AC motor drive. There is no
problem to use with the different voltage and frequency and also can amplify the original characteristic
and life of the motor.
Output Frequency 2
Control mode VF
VFPG
Factory setting: 0.50
Settings 0.00~120.00Hz
Output Voltage 2
Control mode VF
VFPG
Factory setting: 5.0
Settings 0.0V~240.0V
Output Frequency 3
Control mode VF
VFPG
Factory setting: 0.50