Chapter 4 Parameter Settings|DD Series


4-46

Settings 0: Disable

1: Enable

The door width will be difference due to its application. For example, the door of the freight elevator is

much wider than passenger elevator. Therefore, it needs to have door width auto tuning function to

measure the correct door width for the correct position and door open/close. This parameter is suitable

for the condition when door control mode is set to distance control mode (Pr.00-10=0).

The procedure for the door width auto-tuning function:

1. Close the door and make sure it reaches its close complete position, and then open the door to

measure the door width and close the door again to double check the door width.

2. After door width auto-tuning is complete, the measured value will write into Pr.03-12 and Pr.03-13

automatically.

Door close limit
0.0 %

Door open limit
100.0%

Close door (FWD)

Open door (REV)

Close door (FWD)

to make sure the position
of door close limit

measure door width

detect if door width is correct

Door Width Pulses (Unit:1)

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 8800

Settings 1~9999

Door Width Pulses (Unit:10000)

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0

Settings 0~9999

(Unit:10000)

After door width auto tuning (Pr.03-11=1) is completed, door width pulses will write into Pr.03-12 and

Pr.03-13 automatically. User can also manually input door width pulses into Pr.03-12 and Pr.03-13. 。