Chapter 4 Parameter Settings|DD Series


4-69

3.2 Address (Communication Address)

Valid communication addresses are in the range of 0 to 254. A communication address equal to 0, means

broadcast to all AC drives (AMD). In this case, the AMD will not reply any message to the master device.

00H: broadcast to all AC drives

01H: AC drive of address 01

0FH: AC drive of address 15

10H: AC drive of address 16

:

FEH: AC drive of address 254

For example, communication to AMD with address 16 decimal (10H):

ASCII mode: Address=’1’,’0’ => ‘1’=31H, ‘0’=30H

RTU mode: Address=10H

3.3 Function (Function code) and DATA (data characters)

The format of data characters depends on the function code.
03H: read data from register
06H: write single register
Example: reading continuous 2 data from register address 2102H, AMD address is 01H.
ASCII mode:

Command message:

Response message:

STX ‘:’ STX ‘:’

‘0’ ‘0’

Address

‘1’

Address

‘1’

‘0’ ‘0’

Function

‘3’

Function

‘3’

‘2’ ‘0’
‘1’

Number of data

(count by byte)

‘4’

‘0’ ‘1’

Starting address

‘2’ ‘7’
‘0’ ‘7’
‘0’

Content of starting

address 2102H

‘0’

‘0’ ‘0’

Number of data
(count by word)

‘2’ ‘0’

‘D’ ‘0’

LRC Check

‘7’

Content of address 2103H

‘0’

CR ‘7’

END

LF

LRC Check

‘1’

CR

END

LF

RTU mode:

Command message:

Response message:

Address 01H Address 01H

Function 03H Function 03H

21H

Starting data address

02H

Number of data

(count by byte)

04H

00H 17H

Number of data

(count by world)

02H

Content of data
address 2102H

70H

CRC CHK Low

6FH

00H

CRC CHK High

F7H

Content of data
address 2103H

00H

CRC CHK Low

FEH

CRC CHK High

5CH