Chapter 6 Fault Codes and Descriptions |DD Series

6-2

6-1 Common Problems and Solutions

Following fault name will only be displayed when using the digital keypad.

Display

Description

Corrective Actions

Over-current during
acceleration

(Output current exceeds triple
rated current during
acceleration.)

1. Short-circuit at motor output: Check for

possible poor insulation at the output.

2. Acceleration Time too short: Increase

the Acceleration Time.

3. AC motor drive output power is too

small: Replace the AC motor drive with

the next higher power model.

Over-current during
deceleration

(Output current exceeds triple
rated current during
deceleration.)

1. Short-circuit at motor output: Check for

possible poor insulation at the output.

2. Deceleration Time too short: Increase

the Deceleration Time.

3. AC motor drive output power is too

small: Replace the AC motor drive with

the next higher power model.

Over-current during steady
state operation

(Output current exceeds triple
rated current during constant
speed.)

1. Short-circuit at motor output: Check for

possible poor insulation at the output.

2. Check if motor is jammed.

3. AC motor drive output power is too

small: Replace the AC motor drive with

the next higher power model.

Short-circuit is detected
between upper bridge and
lower bridge of the IGBT
module

Return to the factory

Hardware failure in current
detection Over current occur at
STOP

Return to the factory

DC BUS over-voltage during
acceleration (230V: DC 450V)

DC BUS over-voltage during
deceleration (230V: DC 405V)

DC BUS over-voltage at
constant speed (230V: DC
405V)

1. Check if the input voltage falls within

the rated AC motor drive input voltage

range.

2. Check for possible voltage transients.

3.

If DC BUS over-voltage due to

regenerative voltage, please increase the

Deceleration Time or add an optional brake

resistor.