Chapter 4 Parameter Settings|DD Series


4-62

07

Control Parameters

This parameter can be set during operation.

ASR (Auto Speed Regulation) Control (P) of Zero Speed

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 1.5

Settings 0.0~500.0%

ASR (Auto Speed Regulation) Control (I) of Zero Speed

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.050

Settings 0.000~10.000sec

ASR (Auto Speed Regulation) Control (P) 1

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 1.5

Settings 0.0~500.0%

ASR (Auto Speed Regulation) Control (I) 1

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.050

Settings 0.000~10.000sec

ASR (Auto Speed Regulation) Control (P) 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 3.0

Settings 0.0~500.0%

ASR (Auto Speed Regulation) Control (I) 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.100

Settings 0.000~10.000sec

ASR 1/ASR2 Switch Frequency

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 2.00

Settings 0.00~120.00Hz

(0:

disable)

ASR P determines Proportional control and associated gain (P). ASR I determines integral control and

associated gain (I).

When integral time is set to 0, it is disabled. Pr.07-06 defines the switch frequency for ASR1 (Pr.07-02,

07-03) and ASR2 (Pr.07-04, Pr.07-05).

07.06

07.02

07.03

07.04
07.05

Hz

PI

07.00

07.01

0Hz

07.08

07.09

ASR Primary Low Pass Filter Gain

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.008

Settings 0.000~0.350sec

This parameter defines the filter time of the ASR command.