01 Motor Parameters
: This parameter can be set during operation.
Parameter
Explanation
Settings
Factory
Setting VF VFP SVC FO
C
FO
C
01.00 Motor Auto Tuning (PM)
0: No function
1: Auto-tuning for PM motor parameters
(brake locked)
2: Auto-tuning for PG offset angle without
load (Pr.01.09)
3: Auto-tuning for PG offset angle with
load (Pr.01.09)
0
○
01.01 Full-load Current of motor
(PM)
(20~120%)*00.01 Amps
1.00
○
01.02 Rated power of Motor (PM) 0.00~655.35kW 0.06
○
01.03 Rated speed of Motor (rpm)
(PM)
0~65535 250
○
01.04 Number of Motor Poles
(PM)
2~96 16
○
01.05 Rs of Motor parameter
(PM)
0.0~655.35
Ω
13.900
○
01.06 Ld of Motor Parameter
(PM)
0.0~6553.5mH 169.4
○
01.07 Lq of Motor Parameter
(PM)
0.0~6553.5mH 169.4
○
01.08 Back Electromotive Force
(PM)
0.0~6553.5Vrms 0.0
○
01.09 Angle between Magnetic
Pole and PG Origin (PM)
0.0~360.0° 360.0
○
01.10 Magnetic Pole
Re-orientation (PM)
0:No function
1:Reset magnetic pole position
0
○
01.11 Motor Auto Tuning (IM)
0: No function
1: Rolling test
2: Static test
3: Reserved
0
○ ○
01.12 Full-load Current of Motor
(IM)
(20~120%)*00.01 Amps
1.00 ○ ○ ○ ○
01.13 Rated power of Motor (IM) 0.00~655.35kW 0.06
○ ○
01.14 Rated speed of Motor (rpm)
(IM)
0~65535 250
○ ○ ○
01.15 Number of Motor Poles (IM) 2~48 16
○ ○ ○ ○
01.16 No-load Current of Motor
(IM)
00~ Pr.01.12 factory setting
#.## ○ ○ ○
01.17 Rs of Motor (IM)
0.000~65.535
Ω
0.000 ○ ○
01.18 Rr of Motor (IM)
0.000~65.535
Ω
0.000 ○ ○
01.19 Lm of Motor (IM)
0.0~6553.5mH 0.0
○ ○
01.20 Lx of Motor (IM)
0.0~6553.5mH 0.0
○ ○
01.21 Torque Compensation Time
Constant
0.001~10.000sec 0.020
○