5-4 Low Voltage (Lv)

Low voltage

Power cut, including momentary
power l os s

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Restart after r eset

Check if there i s any malfunction
component

i n

power s upply c ircuit

or disconnection

Change defec tiv e component
and chec k c onnection

Check if voltage is
within speci fic ati on

Change power supply
sy stem for requirement

Check if there i s heavy load
with high s tart current in the
same power sy stem

Check if Lv occurs when
breaker and magnetic
contactor is ON

Suitable
transformer

power

capacity

Check if voltage between +1/+2
and - is greater than Pr.06-00

Maybe AC motor drive has malfunction.
Please contact DELTA .

Control c ircuit has malfunction or
misoperation due to noise. P leas e
contact DELTA.

Yes Using the di fferent power

supply for this driv e and
heavy load sy stem