Chapter 2 Wiring|DD Series

2-4

; Damaged insulation of wiring may cause personal injury or damage to

circuits/equipment if it comes in contact with high voltage.

; The AC motor drive, motor and wiring may cause interference. To prevent the

equipment damage, please take care of the erroneous actions of the
surrounding sensors and the equipment.

; The AC drive output terminals U/T1, V/T2, and W/T3 should connect to the

motor terminals U/T1, V/T2, and W/T3 respectively. To reverse the direction of
motor rotation, please switch over any of the two motor leads.

; With long motor cables, high capacitive switching current peaks can cause

over-current, high leakage current or lower current readout accuracy. For
longer motor cables use an AC output reactor.

;

The AC motor drive, electric welding machine and the greater horsepower

motor should be grounded separately.

; Use ground leads that comply with local regulations and keep them as short as

possible.

; Use ground leads that comply with local regulations and keep them as short as

possible.

; Multiple AC drives can be installed in one location. All the units should be

grounded directly to a common ground terminal, as shown in the figure below.

Ensure there are no ground loops.

grouning
terminals

Excellent

grouning
terminals

Good

grouning
terminals

Not allowed