Delta 1.07 VFD-D D User Manual
Page 56
Chapter 4 Parameter Settings|DD Series
4-32
Full-load Current of motor (PM)
Control mode
FOCPM
Unit: Amper
Factory setting: 1.00
Settings (20~120%)*00.01
Amps
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. The factory setting is 90% X rated current.
Example: If rated current for 400W model is 2.5A. The current range for user will be 0.5~3.0A.
(2.5*20%=0.5; 2.5*120%=3.0)
Rated Power of Motor (PM)
Control mode
FOCPM
Factory setting: 0.06
Settings 0.00~655.35
kW
This parameter sets motor’s rated power. Factory setting will be the drive’s power.
Rated Speed of PM Motor (rpm)
Control mode
FOCPM
Factory setting: 250
Settings 0~65535
This parameter sets motor’s rated speed and it must be set according to the specification shown on the
nameplate.
Number of Motor Poles (PM)
Control mode
FOCPM
Factory setting: 16
Settings 2~96
This parameter sets number of motor poles (odd value is invalid).
Rs of Motor parameter (PM)
Control mode
FOCPM
Factory setting: 13.900
Settings 0.0~655.35
Ω
Ld of Motor Parameter (PM)
Control mode
FOCPM
Factory setting: 169.4
Settings 0.0~6553.5mH
Lq of Motor Parameter (PM)
Control mode
FOCPM
Factory setting: 169.4
Settings 0.0~6553.5mH
Back Electromotive Force (PM)
Control mode
FOCPM
Factory setting: 0.0
Settings 0.0~6553.5Vrms
This parameter is used to set back electromotive force (phase-phase RMS value) when the motor is
operated in the rated speed.
It can get RMS value by Pr.01-00=1 (Motor Auto Tuning)
PG Offset Angle (PM)
Control mode
FOCPM
Factory setting: 360.0
Settings
0.0~360.0°
This parameter is to measure the PG offset angle of PM motor.