Chapter 4 Parameter Settings|DD Series


4-32


Full-load Current of motor (PM)

Control mode

FOCPM

Unit: Amper

Factory setting: 1.00

Settings (20~120%)*00.01

Amps

This value should be set according to the rated frequency of the motor as indicated on the motor

nameplate. The factory setting is 90% X rated current.

Example: If rated current for 400W model is 2.5A. The current range for user will be 0.5~3.0A.

(2.5*20%=0.5; 2.5*120%=3.0)

Rated Power of Motor (PM)

Control mode

FOCPM

Factory setting: 0.06

Settings 0.00~655.35

kW

This parameter sets motor’s rated power. Factory setting will be the drive’s power.

Rated Speed of PM Motor (rpm)

Control mode

FOCPM

Factory setting: 250

Settings 0~65535

This parameter sets motor’s rated speed and it must be set according to the specification shown on the

nameplate.

Number of Motor Poles (PM)

Control mode

FOCPM

Factory setting: 16

Settings 2~96

This parameter sets number of motor poles (odd value is invalid).

Rs of Motor parameter (PM)

Control mode

FOCPM

Factory setting: 13.900

Settings 0.0~655.35

Ω

Ld of Motor Parameter (PM)

Control mode

FOCPM

Factory setting: 169.4

Settings 0.0~6553.5mH

Lq of Motor Parameter (PM)

Control mode

FOCPM

Factory setting: 169.4

Settings 0.0~6553.5mH

Back Electromotive Force (PM)

Control mode

FOCPM

Factory setting: 0.0

Settings 0.0~6553.5Vrms

This parameter is used to set back electromotive force (phase-phase RMS value) when the motor is

operated in the rated speed.

It can get RMS value by Pr.01-00=1 (Motor Auto Tuning)

PG Offset Angle (PM)

Control mode

FOCPM

Factory setting: 360.0

Settings

0.0~360.0°

This parameter is to measure the PG offset angle of PM motor.