Multi-function output (mo3) – Delta 1.07 VFD-D D User Manual
Page 65
Chapter 4 Parameter Settings|DD Series
4-41
Multi-function Output (MO3)
Factory setting: 0
Settings Control
mode VF VFPG SVC FOCPG FOCPM
0: No function
○
○
○
○
○
1: AC drive in operation
○
○
○
○
○
2: Zero speed frequency signal (including STOP)
○
○
○
○
○
3: AC drive ready
○
○
○
○
○
4: Low voltage warning(Lv)
○
○
○
○
○
5: Fault indication
○
○
○
○
○
6: Overhead warning (Pr.06.09)
○
○
○
○
○
7: Detection of braking resistor action level
○
○
○
○
○
8: Warning indication
○
○
○
○
○
9: Over voltage warning
○
○
○
○
○
10: OD command
○
○
○
○
○
11: CD command
○
○
○
○
○
12: Demo Indication
○
○
○
○
○
13: Demo complete
○
○
○
○
○
14: Emergency stop indication
○
○
○
○
○
15: Force stop indication
○
○
○
○
○
16: Door open complete (limit) signal output
○
○
○
○
○
17: Door close complete (limit) signal output
○
○
○
○
○
18: Door Close Error
○
○
○
○
○
19: Position Complete Signal
○
○
○
○
○
20: Position Detection 1(for door close only)
○
○
○
○
○
21: Position Detection 2(for door close only)
○
○
○
○
○
22: Position Detection 3(for door close only))
○
○
○
○
○
23: Position Detection 1(for door open only)
○
○
○
○
○
24: Position Detection 2(for door open only)
○
○
○
○
○
25: Position Detection 3(for door open only)
○
○
○
○
○
26: PG feedback error
○
○
○
○
○
27: output signal when unable to open the door
28: over torque (OT1)
These parameters can be used for external terminal output
Summary of Function Settings
Settings
Functions
Descriptions
0
No function
MO has no function.
01
AC drive in operation
The drive is ON when it receives voltage or operation command.
2
Zero speed frequency signal
(including STOP)
Zero speed output signals (including STOP).
3
AC drive ready
Active when the drive is ON and no abnormality detected or
abnormality is cleared.
4
Low voltage warning(Lv)
Active when the detected input voltage is too low.
5
Fault indication
Active when fault occurs.
6
Overhead warning (Pr.06.09) Active when IGBT or heat sink overheats to prevent OH turn off
the drive. When temperature higher than 85 = ON, lower than
℃
<80 = OFF
℃
.
7
Detection of braking resistor
action level
Active when drive begins software braking, this signal can be
used as brake module VFDB action signal or indicator.
8
Warning indication
Active when warning is detected.
9
Over voltage warning
Active when over-voltage is detected.