Door close holding torque, Response time of door close holding torque, Door close high speed 2 – Delta 1.07 VFD-D D User Manual

Page 76: Door close acceleration time 2, Door close deceleration time 2, Door close holding torque level 2, Door close time-out setting, Holding time for cd (close door)terminal

background image

Chapter 4 Parameter Settings|DD Series


4-52

Door Close
Holding Speed

Open Door (R EV)

Door Open Limi t

0.0%

100.0%

Close Door (FWD)

04.00

Door Open

Speed

by Ini tial

04.08

Door Open
Acceleration

Time 1

04.09

Door Open
Deceleration

Time 1

04.03

Door Open H igh Speed 1

04.05

Door Open
Final Speed

04.01

Door Open D istance
by Ini tial Speed

04.04

Door Open

Final Speed

by

Begi ns

04.06

Door Open
by Holding

Speed Begins

04.07

Door Open
Holding Speed

05.03

Door Close

High Speed 1

D oor Clos e

Accel er ation Time 1

05.05

05.04

05.06

Door Close

by Holding
Speed

Begins

05.07

05.09

05.01

Door Close

Distance by
Ini tial Speed

05.00

Door Close

Ini tial Speed

Door Close Limit

Door Close
Final Speed

Door Close
Final Speed

Door Close
by Final Speed

Begi ns

05.08

Door Close Holding Torque

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 20.0

Settings 0.0~100.0% (Drive’s rated current)

Response Time of Door Close Holding Torque

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.20

Settings 0.01~10.00sec

When the door is in the close complete position, it needs holding torque to keep the door still in complete

position. To prevent motor overload, holding torque should be set within a limit.

Door Close High Speed 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 30.00

Settings 0.00~120.0Hz

Door Close Acceleration Time 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 1.0

Settings 0.1~3600sec

Door Close Deceleration Time 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 1.0

Settings 0.1~3600sec

Door Close Holding Torque Level 2

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.0

Settings 0.0~150.0% (Ac drive’s rated current)

Door Close Time-out Setting

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.0

Settings 0.0~180.0sec

(0.0sec:Disable)

When the time for door closing is longer than the setting in Pr.05-17, door will re-open.

Holding Time for CD (Close Door)Terminal

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0.0

Settings 0.0~999.9sec (999.9sec is always holding)

This parameter is used to clear the CD terminal signal (door close signal) when door open complete.

During the holding period, AC Motor Drive will still be in RUN status. After holding time, AC Motor Drive