This parameter determines the PWM carrier frequency of the AC motor drive.

1kHz

8kHz

15kHz

Carrier

Frequency

Acoustic
Noise

Electromagnetic
Noise or leakage

current

Heat

Dissipation

Current

Wave

Significant

Minimal

Significant

Minimal

Minimal

Significant

Minimal

Significant

From the table, we see that the PWM carrier frequency has a significant influence on the

electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise. If noises from

ambient environment is greater than motor noise, lower PWM carrier frequency will help to lower the

temperature of AC motor drive. When PWM carrier frequency is high, though the drive will operate more

quietly, but wiring and interference may have problem.

Model

VFDXXXDDXXE:

Settings

02~10kHz

Auto Voltage Regulation (AVR) Function

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0

Settings 0: Enable AVR

1: Disable AVR

2: Disable AVR when deceleration stop

The rated voltage of the motor is usually AC220V/200V 60Hz/50Hz and the input voltage of the AC motor

drive may vary between 180V to 264 VAC 50Hz/60Hz. Therefore, when the AC motor drive is used

without AVR function, the output voltage will be the same as the input voltage. When the motor runs at

voltages exceeding the rated voltage with 12% - 20%, its lifetime will be shorter and it can be damaged

due to higher temperature, failing insulation and unstable torque output.

AVR function automatically regulates the AC motor drive output voltage to the Maximum Output Voltage

(Pr.1-02). For instance, if Pr.1-02 is set at 200 VAC and the input voltage is at 200V to 264VAC, then the

Maximum Output Voltage will automatically be reduced to a maximum of 200 VAC.

When motor stops with deceleration, it will shorten deceleration time. When setting this parameter to 02

with auto acceleration/deceleration, it will offer a quicker deceleration.

Source of the Master Frequency Command

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 1

Settings 0: by digital keypad input

1: by external terminal

2: by RS-485 serial communication

This parameter is used to set the source of the operation command.

Demo Mode

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0

Settings 0: Disable

1: Display demo action

Frequency Testing Command

Control mode VF

VFPG

SVC

FOCPG

FOCPM

Factory setting: 0

Settings 0~120.00Hz