Door close error deceleration time, Door re-open detection time – Delta 1.07 VFD-D D User Manual
Page 79
Chapter 4 Parameter Settings|DD Series
4-55
Larger current is required at the beginning of door open and door close, so it needs to have larger
re-open current level in the acceleration area. Please refer to the following figure for setting reopen
current and acceleration area:
Door Close
Holding Speed
Open Door ( REV)
Clos e Door (FWD)
04.00
Door Open
Speed
by Ini tial
04.08
Door Open
Accel eration
Time 1
04.09
Door Open
Deceleration
Time 1
04.03
Door Open H igh Speed 1
04.05
Door Open
Final Speed
04.01
Door Open D istance by
Ini tial Speed
04.04
Door Open
by Final Speed
Begi ns
04.06
Door Open
by Holding Speed
Begi ns
04.07
Door Open
Holding Speed
05.03
Door Close
High Speed 1
05.08
D oor Clos e
Ac celerati on Time 1
05.05
05.04
05.06
Door Close
by Holding
Speed
Begins
05.07
05.09
05.01
Door Close
Distance by
Ini tial Speed
05.00
Door Close
Ini tial Speed
Door Close
Final Speed
Door Close
Final Speed
Door Close
by Final Speed
Begi ns
Door Open Li mit
100.0%
Re-open Detected Area
Door Close Limit
0.0%
05.25
Door reopen current level 1
05.25 * 04.11/100
Door Re-open Current Level
for Acceleration Area
05.32
Door Re-open
Accel eration
Boundary
05.31
Door Re-open
Low Speed Boundary
Door Close Error Deceleration Time
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.4
Settings 0.1~3600sec
Door Re-open Detection Time
Control mode VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.2
Settings 0~10.0sec