beautypg.com

Motorola 68P02958C00-B User Manual

Page 432

background image

Error Messages

C-140

Error #241:

Txintrc or Rxintrc was called with invalid type %%

Invalid parameter type. See Intrac Protocols chapter in Advanced Features in
the Application Programmer manual.

Error #242:

Intrac/Meic port not created

The appropriate port must be defined in Site Configuration.

Error #243:

One of the following calls: Txintrc, Txwidth, Rxintrc, Rxwidth, Rxiupd failed
getting pointer to value at intrac system table

May indicate system software problem. Consult product group.

Error #244:

Txintrc was called with ITxStt=0 or Txwidth was called with Tx_len=0

Illegal value set in application.

Error #245:

#the 'Load' option was used to download the application, however the number of
diffrentiators were changed.

You should use the 'Reset Load' option instead and then do Download.

Error #250:

Cannot read module type at: %%

I/O module defined but physically missing.

Error #251:

Module type does not match site configuration, module: %%

Incompatible module type. Configuration definition and physical module are
different.

Error #252:

Module: %%, initial values are invalid.

There are no preset values in the control registers of the DO module gate array.

Error #253:

Digital output module: %%, desired values in gate array are not equal to image
in memory.

The gate array data and the image in the RTU do not match.

Error #254:

Digital output module: %%, actual values of relays are not equal to desired
values in gate array.

The gate array data and the image in the RTU do not match.

Error #255:

I/O module: %% analog input not calibrated.

At least one of the analog input in the module is not calibrated.

Error #256:

Cannot 'communicate' with module: %%

It is not possible to read data from the module; it is faulty.