Configuration – Motorola 68P02958C00-B User Manual
Page 245

Adding Terminal Server Ports
6-10
MOSCAD
8 Pin Connector
RJ 45 Connector
EQUINOX
8 Pin Connector
RJ 45 connector
1 (TXD)
6 (RxD)
2 (RXD)
4 (TxD)
3 (CTS)
7 (DTR)
4 (GND)
3 (GND)
5 (CD)
8 (RTS)
6 (RTS)
2 (DCD)
(*) 7 (12V)
N.C
8 (DTR)
1 (CTS)
Configuration
General notes:
•
The commands to be entered were given under the assumption that the ELS16 is
performing a ‘self boot’. In case of a boot server, please refer to EQUINOX
documentation.
•
Commands can be typed in lower case or in upper case letters.
•
After each command, press the
ELS16 prompts: “Local>“
•
N represents a port number. It can be any number in the range of 1 to16
•
t represents a value in seconds between 10 and 180
•
a and m represents a number in the range of 0..255
•
SOCKET_NUMBER represent a TCP socket. Each port must have a deferent TCP
socket number, which must be greater than 2001 or equal.
•
SERVICE_NAME is a string given to a service as its’ name.
•
The first command to be entered will allow the user access to EQUINOX configuration.
The default password is SYSTEM.
After attaching a console terminal (usually at port 1), type in the following commands.
SET PRIV < return>
SYSTEM